72
Control
7. Close the AHU Kit enclosure again (see “4.1 Installation of AHU Kit“ – step 5).
8. Via the signal wiring from the external BMS, which is now connected to contacts AI3 and AI4
(see step 2), select the 0–10 V demand control functionality as follows:
Input
Voltage* (V)
0 – 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0 9.5 – 10.0
Demand (%
of nominal
current)
Stop
1
40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 No limit
2
Thermo-Off
3
* If a voltage range (0 – 0.5 or 9.5 – 10.0 V) is indicated, the applied voltage must be within the given limits.
However, if a single value (e.g. 1.0 V) is indicated, the applied voltage must be within +/–0.1 V of the given value to achieve the assigned demand setting.
Examples: “Stop“ can be achieved with any analogue input value greater than 0 V and less than or equal to 0.5 V;
40 % demand can be achieved with any analogue input value greater than or equal to 0.9 V and less than or equal to 1.1 V etc.
1 Stop: AHU system / indoor unit is completely switched off.
2 No Limit: No restrictions applied by BMS to AHU system / indoor unit performance (equivalent to “full-load operation“ of AHU system / indoor unit.
3 Thermo-Off: No cooling / heating operation (compressor is switched off; however, the fans may still be operating). For example, forced Thermostat-Off
mode can be used for free cooling.
7.2.4 Error Codes
Error Code Meaning
HHH Sensor breakage or polarity inversion.
Measured value is above the valid upper limit.
LLL Sensor short-circuit or polarity inversion.
Measured value is below the valid lower limit.
7.2.5 Maintenance and Service
In normal operation, the thermostat is maintenance-free.
To prolong its lifecycle, the following precautions should be observed:
● Protect the electronic components from condensation moisture.
● Avoid touching the buttons with ngernails or other pointed objects to prevent
damage or premature wear of the touch-senstive buttons.
● Prevent excessive dust formation on the controller.
● Occasionally clean the front side of the controller with a damp cloth while the
controller is switched off.