Control
4. Press the button repeatedly to select the entry “PSL”.
repeatedly
5. Use the and buttons to change the value to either “0” (= factory setting) for „heat-
ing mode“ or “1” for „cooling mode“.
6. Conrm the complete parametrization by pressing and holding the button for approxi-
matedly 3 seconds.
1 x for 3 sec.
Parametrization is now complete. The PV and SV displays have returned to showing the cur-
rent temperature and the set temperature values respectively.
Switching from 0–10 V to 2–10 V output signals
The voltage range for the output signals on terminals 6–7 is factory-set to 0–10 V.
Switching the voltage range from 0–10 V to 2–10 V is possible. However, Panasonic recom-
mends to keep the factory setting.
To switch from 0–10 V to 2–10 V output signals, perform the following steps:
1. Press and hold the and buttons jointly for approximately 5 seconds.
1 x 2 buttons for 5 sec.
The PV display shows “PAS”, while the current setting (“0”) in the SV display is blinking.
Note: After 30 seconds of idleness, the display automatically returns from parametrization
view to normal view.
2. Use the , and buttons to change the value to “–72” (minus 72).
3. Conrm the new setting by pressing the button.
1xbriey
The PV display now shows “nun”, while the SV display now shows “3”.
4. Press the button repeatedly to select the entry “AO”.
repeatedly