Product description
CZ-CAPBC2 Mini seri-para I/O unit (advanced version only)
Easy integration in external AHU control systems and BMS
Demand control: 40 to 115 % (5 % steps) of nominal current by 0–10 V input
signal*
Target temperature setting by 0–10 V or 0–140 Ω input signal*
Room supply air temperature output by 4–20 mA signal
Mode select or/and ON/OFF control
Fan operation control
Operation status output/ Alarm output
Thermostat ON/OFF control
* Demand control by external BMS cannot be combined with the demand control or target temperature setting accom-
plished by the thermostat. However, if simultaneous demand control and target temperature setting is needed, this
can only be achieved by using a second (optional) CZ-CAPBC2 interface.
PAW-T10 PCB to connect to T10 connector
Dry contact PCB for easy control of the unit
Operation ON/OFF input signal
Remote control prohibition
Operation ON status output signal, maximum 230 V / 5 A (NO/NC)
Alarm status output signal, maximum 230 V / 5 A (NO/NC)
PAW-OCT, DC12 V outlet, OPTION terminal
Output signal for Cooling/Heating/Fan status
Output signal for Defrost operation indication
Output signal for Thermostat-ON status
Additional contacts available
External humidier control (ON/OFF) 230 V AC 3 A
External fan control (ON/OFF) 12 V DC
External lter status signal potential free
External oat switch signal potential free
External leakage detection sensor or TH. OFF contact potential free (possible
usage for external blow out temperature control)