Electrical Wiring
6. Use the standard power supply cables for Europe (such as H05RN-F or
H07RN-F which conform to CENELEC(HAR) rating specications) or use the
cables based on IEC standard (245 IEC57, 245 IEC66).
7. When linking the outdoor units in a network, disconnect the terminal extended
from the short plug from all but one of the outdoor units. (When shipping: in
shorted condition.)
For a system without link (no wiring connection between outdoor units), do not
remove the short plug.
8. Do not install the inter-unit control wiring in a way that forms a loop.
Outdoor unit Outdoor unit
Outdoor unit
Indoor unit Indoor unit Indoor unit
Prohibited
Prohibited
Indoor unit Indoor unit
9. Do not install inter-unit control wiring such as star branch wiring. Star branch
wiring causes faulty address setting.
Outdoor unit Indoor unit
Indoor unit
Indoor unit
Indoor unit
Branch point
Prohibited
10. If branching the inter-unit control wiring, the number of branch points should be
16 or fewer. (Branches that are less than 1m are not included in the total branch
number.)
Outdoor unit Outdoor unit Outdoor unit
Indoor unit
Indoor unit
Indoor unit
more than 1 m
more than 1 m
more than 1 m
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Branch
point
16 or fewer