20
Intakeairtemperature
Evaporater
temperature
10
2
Start
Stop
1.5
BasicTime
Comp.
IndoorFan
OutdoorFan
OperationIndicator
1 1
3
7
Operationstatus
Timedelaysafetycontrol
CompressorTestcontrol
Autorestartcontrol
Anti-freezingControl
Time
d-g
g-h
h-o
q-t
:
:
:
:
Operate
Stop
abcdefghijklmnopqrstuvwxyz
3
4
1
TimeGraphforCoolingOperation
Settemperature
31
29
8.2.SoftDryModeOperation
WhenselectingSoftDrymodeoperation,theoperationwillbecoolinguntiltheroomtemperaturereachesthesettempon
remotecontrol,andthenSoftDrywillbeactivated.(DuringSoftDryModethefanofindoorunitwilloperateatsuperlow
speed.Thesoftdrymodewillrunforlessthan10minutes.)
OnceSoftDrymodeoperationisturnedoff,indoorfan,compressorandoutdoorfanwillstopfor6minutes.
COOLING(OFF)
DRY(ON)
DRY(OFF)
DRY
COOLING
COOLING(ON)
DRY(ON)
1.5
1.0
DRY(OFF)
Operationarea
TimeDelaySafetyProtection
Duringcoolingmodeoperation,ifthecompressorceased,itwillnotrestartwithin3minutes.
AntiFreezingControl
SameasthedenotationinCoolingOperation.()
(DuringSoftDryModeOperation,compressorwillstopforatleast6min.)