3-53. External Electronic Expansion Valve Kit (CZ-P56SVK1U)
Precautions in this manual are given in the form of “Warnings” or “Cautions. Both types of precautions contain
important information related to your safety, the safety of users, and the correct operation, installation, or
maintenance of the air conditioning system. Be sure to carefully observe all relevant precautions.
WARNING
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or
death.
CAUTION
This symbol refers to a hazard or unsafe practice which can result in personal injury or
product or property damage.
This external electronic expansion valve is compatible with the refrigerants listed below.
R410A, R407C, R22
1. Checking Parts
Please check these parts below that came in the box.
Description Shape Q’ty Description Shape Q’ty
1
External electronic
expansion valve
(Extension cord 26.2 ft.)
1
3
Clamp
(Large: 13-25/32",
Small: 7-7/8")
Large: 2
Small: 4
4 Installation manual
1
2 Flare insulator
2 5 Insulating tape
White
(heat resisting)
2
2. Positioning for Installation
The valve should be connected to the liquid tube. Determine the position for installation referring to the diagram of
outer dimensions. (Fig. 3-170) Refrigerant-fl ow noise may occur from the external electronic expansion valve. As a
guide, the distance from the indoor unit should be a minimum of 16.4 feet, but less than 26.2 feet. (Install away from
locations where strictly quiet operation is required.)
If this distance is unavailable, install inside the ceiling or in another location where noise insulation is possible.
This is a functional component, and therefore may require inspection and replacement. Consider this when deciding
the installation location. (For example, place near an inspection port, or provide one.)
This valve is for indoor use. Do not install the valve outdoors.
Diagram of outer dimensions
(8-5/64)
Type
A
B
56
12-51/64
o 1/4
160
14-11/64
o 3/8
A
(10-53/64)
Extension cord (26.2 ft.)
Connecting portion B
Connecting portion B
Outdoor
side
Indoor
side
(2-3/4)
Unit: in.
Fig. 3-170
VRF_Indoor_US.indb 54VRF_Indoor_US.indb 54 2011/09/30 12:23:112011/09/30 12:23:11