Panasonic ECOi 2 Way Installationshandbuch

Stöbern Sie online oder laden Sie Installationshandbuch nach Split-System-Klimaanlagen Panasonic ECOi 2 Way herunter. Panasonic ECOi 2 Way Installation Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 52
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
External diameter of service port R410A: 5/16"
NOTE
This air conditioner uses the refrigerant R410A.
INSTALLATION INSTRUCTIONS
2WAY VRF System Air Conditioner
85464369527012 CV6233186894
U
Type
Type
Type
2WAY VRF System
U-72ME1U9 U-96ME1U9
U-72ME1U9E* U-96ME1U9E*
Outdoor Unit Type 9672
Outdoor Units
Model No.
*
1
Necessary to install the External Electronic Expansion Valve Kit (Optional : CZ-P56SVK1U)
* Salt-Air Damage Resistant Specifications.
Indoor Unit Type 7 9 12 15 18
S-12MD1U6S-09MD1U6S-07MD1U61-Way CassetteD1
S-18MU1U6S-12MU1U64-Way CassetteU1
Y1 4-Way Cassette 60 × 60 S-12MY1U6 S-18MY1U6
K1 Wall Mounted S-07MK1U6 S-09MK1U6 S-12MK1U6 S-18MK1U6
S-18MT1U6S-12MT1U6CeilingT1
F1 Low Silhouette Ducted S-07MF1U6 S-09MF1U6 S-12MF1U6 S-15MF1U6 S-18MF1U6
S-07MM1U6 S-09MM1U6 S-12MM1U6 S-15MM1U6 S-18MM1U6M1 Slim Low Static Ducted
E1 High Static Pressure Ducted
S-18MP1U6S-15MP1U6S-12MP1U6S-09MP1U6S-07MP1U6
S-18MR1U6S-15MR1U6S-12MR1U6S-09MR1U6S-07MR1U6
Floor StandingP1
R1 Concealed Floor Standing
Indoor Unit Type 19 24 36 48 54
D1 1-Way Cassette
U1 4-Way Cassette S-36MU1U6
Y1 4-Way Cassette 60 × 60
S-19MS1U6*
1
Wall MountedK1
T1 Ceiling S-24MT1U6
F1 Low Silhouette Ducted S-24MF1U6
S-24MU1U6
S-24MK1U6
S-36MF1U6 S-48MF1U6 S-54MF1U6
M1 Slim Low Static Ducted
E1 High Static Pressure Ducted S-36ME1U6 S-48ME1U6
P1 Floor Standing S-24MP1U6
S-24MR1U6R1 Concealed Floor Standing
Indoor Units
Seitenansicht 0
1 2 3 4 5 6 ... 51 52

Inhaltsverzeichnis

Seite 1 - INSTALLATION INSTRUCTIONS

External diameter of service port R410A: 5/16"NOTEThis air conditioner uses the refrigerant R410A.INSTALLATION INSTRUCTIONS2WAY VRF System Air C

Seite 2 - IMPORTANT!

101-9. System LimitationsMax. No. allowable connected outdoor units 3 *1Max. capacity allowable connected outdoor units 288,000 BTU/h (24 ton, 84.4

Seite 3 - Check of Density Limit

WARNINGAlways check the gas densitylimit for the room in which theunit is installed.1-10. Check of Limit DensityWhen installing an air conditioner in

Seite 4 - Vacuum pump

121-12. Optional Distribution Joint KitsSee the installation instructions packaged with the distribution joint kit for the installation procedure.Tab

Seite 5

134-21/64 3-13/16 4-21/64 3-13/16 4 6 / 3 5 - 2 4 6 / 3 5 - 2 Insulation B A D B B C C C DE A C D E CDistr ib utio n Joint Insulation Distr ib utio n

Seite 6 - CONTENTS

1-13. Example of Tubing Size Selection and Refrigerant Charge Amount 1 2 3 4 LA LB LC A B Outdoor unit 96 type 96 type48 type 48 type 48 type36

Seite 7 - 1. GENERAL

●Obtain liquid tubing size from Tables 1-3, 4, 5, 7 and 10-1.Main tubingLA = ø5/8 (ft.) (Total capacity of indoor unit is 179,400 BTU/h) The longest t

Seite 8 - Explanation of symbols

16Fig. 2-1Fig. 2-2Fig. 2-32. SELECTING THE INSTALLATION SITE2-1. Outdoor UnitAVOID:●heat sources, exhaust fans, etc.●damp, humid or uneven locations

Seite 9 - ( A – C)

2-3. Shield for Horizontal Exhaust DischargeIt is necessary to install an air-discharge chamber (fieldsupply) to direct exhaust from the fan horizont

Seite 10 - 42 oz/unit 42 oz/unit

33-3/16 33-3/16 33-3/1633-3/1621106-1/8106-1/8106-1/874-1/1674-1/1674-1/16(32-1/8)(32-1/8)35-1/4(Maximum bracket dimensions)35(Ceiling panel dimension

Seite 11 - 1-10. Check of Limit Density

106-1/8106-1/87474-1/16(32-1/8)Air direction: Front directionAir direction:Right directionCeiling panel Ceiling panelTop view (Before installation of

Seite 12

2IMPORTANT! Please Read Before StartingThis air conditioning system meets strict safety and oper-ating standards. As the installer or service person,

Seite 13

3. HOW TO INSTALL THE OUTDOOR UNIT3-1. TransportingWhen transporting the unit, have it delivered as close to the installation site aspossible withou

Seite 14 - 48 type 48 type 48 type

21Fig. 3-6Remove 2 screwsTubing coverBottomFrontRemove 11 panel screws from front panelUse cutting pliers or similar tool to cut cover outFig. 3-5Inde

Seite 15

223-4. Prepare the Tubing● Material: Use C1220 phosphorous deoxidized copper as described in JIS H3300, “Copper and Copper Alloy Seamless Pipesand Tu

Seite 16 - 2-1. Outdoor Unit

23● Precautions for brazingBe sure to replace the air inside the tube with nitrogen to prevent oxide film from forming during the brazing process. Be

Seite 17 - Fallen snow

24Control wiring (A) Inter-unit (between outdoor and indoor units) control wiring*(B) Remote control wiring (C) Control wiring for group control (D

Seite 18 - 3-unit installation

21B13Remote ControllerCONNECTOR2P (WHT)RC(BLU)WHTBLKWHTBLKWHTBLKWHTBLK* Disconnect switch (Field Supply)******U2U1L2L1R2R1423121WHTRemote Controller

Seite 19

26Outdoor unit Outdoor unit Outdoor unitIndoor unit Indoor unit Indoor unit Indoor unitIndoor unitmore than 3.3 ft.more than 3.3 ft.Branchpoint16 or f

Seite 20 - 3-1. Transporting

27Fig. 4-4Stranded wireRingpressureterminalStrip 3/8"Fig. 4-5Screw and Special washerRingpressureterminalWireTerminal plateRing pressure terminal

Seite 21 - 3-3. Routing the Tubing

285. HOW TO PROCESS TUBINGThe liquid tubing side is connected by a flare nut, and thegas tubing side is connected by brazing.5-1. Connecting the Ref

Seite 22 - 3-5. Connect the Tubing

29Caution Before Connecting Tubes Tightly(1) Apply a sealing cap or water-proof tape to prevent dustor water from entering the tubes before they are u

Seite 23

3t o a r h nt w n n-Check of Density LimitThe room in which the air conditioner is to beinstalled requires a design that in the event of refrig-erant

Seite 24 - Outdoor unit

30Unit sideinsulatorInsulation tape (white)(supplied)Sealer (supplied)Flare insulator (supplied)Tube insulator(not supplied)Heat resistant248°F or abo

Seite 25 - 4-3. Wiring System Diagram

31Fig. 5-9Fig. 5-105-4. Taping the Tubes(1) At this time, the refrigerant tubes (and electrical wiringif local codes permit) should be taped together

Seite 26

32Fig. 6-1Fig. 6-2Fig. 6-36. AIR PURGINGAir and moisture in the refrigerant system may have undesirable effects as indicated below.●pressure in the s

Seite 27 - Stranded wire

33Fig. 6-4(4) Do a leak test of all joints of the tubing (both indoor andoutdoor) and both gas and liquid service valves. Bub-bles indicate a leak. Wi

Seite 28 - 5. HOW TO PROCESS TUBING

34Fig. 6-5Fig. 6-6(2) When the desired vacuum is reached, close the “Lo” knob ofthe manifold valve and turn off the vacuum pump. Pleaseconfirm that th

Seite 29 - Outdoor Units

357. TEST RUN7-1. Preparing for Test Run●Before attempting to start the air conditioner, checkthe following.(1) All loose matter is removed from the

Seite 30 - Two tubes arranged together

Does system operate? NO *2 *1 *3 *2 *3 *4 *4 CASE 3A YES YES NO YES NO NO NO YES YES YES Refer to Fig. 7-4Recheck the items to check before the test r

Seite 31 - 5-4. Taping the Tubes

377-3. Main Outdoor Unit PCB SettingCN003CN101CN100S003 S002S004S005S006S007Fig. 7-4

Seite 32 - 6. AIR PURGING

38Examples of the No. of indoor units settings (S005, S004)z2321ON1ONON312321ON311111ON123ON123ON123ON12321ON21ONON1221ON1100ON123ONOFFONOFFONOFFONOFF

Seite 33

7-4. Auto Address Setting1. Auto Address SettingBasic wiring diagram: Example (1)• If link wiring is not used(The inter-unit control wires are not c

Seite 34

Newtool?1-2. Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A refriger-ant deterioration and co

Seite 35 - 7. TEST RUN

401-1 1-29-22-21-231-13-123921ON3ON123ON123321ONON123ON122ON1311ON32ON122ON13321ONONOFFONOFFONOFFONOFFONOFFONOFFONOFFONOFFONOFFONOFFOFFONAutomatic add

Seite 36 - 7-2. Test Run Procedure

41Case 2 Automatic Address Setting (no compressor operation)Indoor and outdoor unit power can be turned ON for each system separately.Indoor unit ad

Seite 37 - S006S007

42Automatic Address Setting in Heating Mode● Indoor and outdoor unit power cannot be turned ON for each system separately. In the following, automati

Seite 38

43Automatic Address Setting in Cooling Mode● Indoor and outdoor unit power cannot be turned ON for each system separately. In the following, automati

Seite 39 - Fig. 7-5

44is blinkingLED 1 LED 2( : ON : Blinking : OFF)Display meaningAfter the power is turned ON (and automatic address setting is not in progress), no

Seite 40 - Fig. 7-6

45Request concerning recording the indoor/outdoor unit combination Nos. After automatic address setting has been completed, be sure to record them for

Seite 41

46CAUTION● This outdoor unit cannot collect more than the ratedrefrigerant amount as shownby the nameplate on the back.● If the amount of refrigerant

Seite 42 - Heating mode

7-7. Meaning of Alarm MessagesTable of Self-Diagnostics Functions and Description of Alarm DisplaysAlarm messages are indicated by the blinking of LE

Seite 43 - Cooling mode

Possible cause of malfunction Protectivedevice forcompressor isactivatedCurrent is not detected when comp. No. 1 is ON.EEP ROM on indoor unit PCB fail

Seite 44 - Display meaning

Alarm messages displayed on system controllerIndoor or main outdoor unit is not operating correctly.Mis-wiring of control wiring between indoor unit,

Seite 45

5ValveLiquid3-2. Use R410A exclusive cylinder only.Single-outlet valve(with siphon tube)Liquid refrigerant should be rechargedwith the cylinder standi

Seite 48 - Continued

DC0811-21111Printed in Japan

Seite 49

6IMPORTANT! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Please Read Before StartingCheck of Density LimitPrecautions for Installation

Seite 50

7Table 1-1 Outdoor Unit1-2. Accessories SuppliedSee Table 1-1.1-1. Tools Required for Installation (not supplied)1. Flathead screwdriver2. Phillips

Seite 51

Explanation of symbolsDistribution joint (CZ :purchased separately)Solidly welded shut (pinch weld)Balance tubing(ø1/4")Ball valve (field supply)

Seite 52 - Printed in Japan

18192,000(56.3)16672,000(21.1)96,000(28.1)8U-72ME1U9(E)U-72ME1U9(E)U-72ME1U9(E)U-96ME1U9(E)U-96ME1U9(E)U-96ME1U9(E)U-72ME1U9(E)U-72ME1U9(E)U-72ME1U9(E

Kommentare zu diesen Handbüchern

Keine Kommentare