INSTALLATION INSTRUCTIONSCS-KE12NB41 & CZ-18BT1U + CU-KE12NK1CS-KE18NB4UW & CZ-18BT1U + CU-KE18NKU(852-6-4190-577-00-2)APPENDIX BA-2

Seite 2 - Split System Air Conditioner

9Amust be within the range of 1/2"(13mm) to 23/32"(18mm). (Fig. 6-11)If not within this range, malfunction or other trouble may occur.Ceilin

Seite 3 - Please Read Before Starting

10(2) Removing the corner cover andindicator covera) While lightly pressing the cen-ter of the corner cover, pull upthe tab for the screw hole.Use the

Seite 4 - When Servicing

11Fig. 6-23Fig. 6-24 Fig. 6-25fit into the holes in the ceiling panel.Place the corner cover so that the 3 tabsThen fasten it in place with the suppli

Seite 5 - 1. General

3-7. Wiring InstructionsGeneral precautions on wiring(1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate,then carry ou

Seite 6 - Outdoor unit

13Cross-Sectional (A)+(B) (A) Power Supply Wiring Length (ft) (C) ControlFuse or Circuit Area (AWG)(B) Power Line Length (ft) Line Length (ft)Model (#

Seite 7 - About 4" (10 cm)

14When connecting each power wire to the corresponding terminal, fol-low the instructions “How to connect wiring to the terminal” and fastenthe wire s

Seite 8

15 For stranded wiring(1) Cut the wire end with a cutting pliers, then strip the insulation to expose the stranded wiring about 3/8" (10 mm) and

Seite 9

165. Refrigerant Tubing5-1. Use of the Flaring MethodMany of the conventional split system air conditionersemploy the flaring method to connect refr

Seite 10 - Indoor unit

175-4. Connecting Tubing between Indoor and Outdoor Unitsa) Tightly connect the indoor side refrigerant tubing exten-ded from the wall with the outdoo

Seite 11

Be sure to use a manifold valve forair purging. If it is not available, usea stop valve (field supply) for thispurpose. The “Hi” knob of the mani-fold

Seite 12 - * The grille can be installed

This air conditioner uses the refrigerant R410A.External diameter of service port R410A: 5/16"Split System Air Conditioner85264190577002 2011INST

Seite 13

19(4) With the “Lo” knob of the manifold valve open, runthe vacuum pump. The operation time for the vacu-um pump varies with tubing length and the cap

Seite 14 - Terminal Terminal

20How to Test Run the Air ConditionerAfter turning on the power of the air conditioner, use theremote controller and follow the steps below to conduct

Seite 15 - Strip 15/16" (25 mm)

21 Pump DownPump down means collecting all refrigerant gas in thesystem back into the outdoor unit without losing any ofthe gas. Pump down is used wh

Seite 16 - Stranded wire

227. Remote Controller Installation PositionThe remote controller can be operated from either anon-fixed position or a wall-mounted position.To ensur

Seite 17 - 5. Refrigerant Tubing

23ACL(Reset)button1HR.TIMERbuttonON/OFFoperationbuttonHIGH POWERbutton8. Address Switch8-1. Address Setting of the Remote ControllerThe address can

Seite 18

2IMPORTANT! Please Read Before StartingThis air conditioning system meets strict safety and operatingstandards. As the installer or service person, it

Seite 19 - 6. Air Purging

3 8VHWKHIODUHPHWKRGIRUFRQQHFWLQJWXELQJ $SSO\UHIULJHUDQWOXEULFDQWWRWKHPDWFKLQJVXUIDFHVRIthe flare and union tubes before connecting the

Seite 20

4Printed on container boxFor unit & PVCtube connectionFor drain hoseconnectionRemarksQ’tyFor full-scaleinstallationdiagram12444421For temporarilys

Seite 21

51-5. Additional Materials Required for Installation1. Refrigeration (armored) tape2. Insulated staples or clamps for connecting wire(See local codes

Seite 22 - Pump Down

62-2. Outdoor UnitAVOID: heat sources, exhaust fans, etc. (Fig. 3) damp, humid or uneven locations.DO: choose a place as cool as possible. choose

Seite 23 - Service Valve Connections

7Hole-in-anchorConcrete InsertSuspension bolt (M10 or 3/8")Hole-in-plug(locally purchased)Fig. 6-123-5/8"(600mm)21-1/32"(534mm)Ceiling

Seite 24 - 8. Address Switch

8 In cases where it is necessary to raise the height of thedrain piping, the drain piping can be raised to a maximumheight of 2.78 ft. (850 mm) above