Split System Submittal Data
Outdoor: CU-4KS31NBU
MultiSystem - Outdoor
Approval:
Date:
Construction:
Unit#:
Drawing#:
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
General Data
Power (V/P/Hz) 208/230/1/60
Circuit Ampacity (A) 17
Fuse Size, Max.(A) 20
Compressor DC Twin Rotary
No. Used 1
R.L. Amps - L.R. (A) 12.3-17
Crankcase Heater (A) N/A
Outdoor Unit
Fan Type Propeller
Dia & Length (in.) - No. Speeds D18-1/8 - 1
Type Drive - No. Speeds DC Motor
No. Poles (RPM) 8 - (800)
No. Motors (W) 1-(90)
CFM (High) 1942
F.L. Amps (A) 0.55
Coil Type Aluminum Fin & Copper Pipe
Fin Type - Pipe Type Corrugated Plate - Inner Riffeled
Rows - F.P.I. 2 - 18.1
Face Area (sq.ft.) 7.75
Tube Size (in) 3/8”
Refrigerant R410A
Lbs. - R410a 8.38
Control Electronic Expansion Valve
Line Size (in. O.D. Discharge) 1/4” x 4 (Flare)
Line Size (in. O.D. Suction) 3/8” x 2 + 1/2” x 2 (Flare)
Dimensions (HxWxD)
Indoor Unit (Crated) (in.) 40-1/8 x 41 11/32 x 16 21/32
Indoor Unit (Uncrated) (in.) 35 1/32 x 35 7/16 x 12 19/32
Weight (lbs.)
Net 174.2
Shipping 183
Shipping Volume (cu.ft.) 15.88
Performance Data @ ARI Standard Conditions (230/208V)
Cooling
Total Capacity (BTU/H) 30,600 (9,800 - 30,600)
Sensible Capacity (BTU/H) 25,800
Latent Capacity (BTU/H) 4,800
SEER 17.6
Amps (A) 12.3
Max. Amps (A) 17
Power Inputs (KW) 2,800
Max. Inputs (W) 4,000
Outdoor Sound Rating (dB-A) 53
Operating Range
Indoor Air Intake Temp
Outdoor Air Intake Temp
Cooling (Max) 95F DB/71F WB 115 F DB
Cooling (Min) 67 DB/57F WB 14 F DB
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - Split System Submittal Data

Split System Submittal DataOutdoor: CU-4KS31NBUMultiSystem - OutdoorApproval:Date:Construction:Unit#:Drawing#:Job Name:Location:Engineer:Submitted to:

Seite 2 - Outdoor Dimensions

Panasonic North AmericaAir Conditioning Division1690 Roberts Blvd., NW, Suite 110Kennesaw, GA 30144http://www.panasonic.com/airconOutdoor DimensionsWi

Kommentare zu diesen Handbüchern

Keine Kommentare